Licensing Guidance Frameworks: Difference between revisions
Line 24: | Line 24: | ||
<br><br> | <br><br> | ||
In current practice, advanced reactor vendors develop a generic design phase PRA or a reference plant PRA | In current practice, advanced reactor vendors develop a generic design phase PRA or a reference plant PRA. A Level 1 PRA or both Level 1 and Level 2 PRAs may be requested by the applicable regulatory authority for each new reactor project. A Level 3 PRA is typically not developed or requested by the regulatory authorities for new reactors. However, a Level 3 PRA could support the definition of [https://www.oecd-nea.org/upload/docs/application/pdf/2021-02/csni-r2012-17.pdf exclusion zones] [[References|[25]]]. In the US, the Licensing Modernization Project (LMP) has developed a methodology that uses standard safety analyses like Process Hazards Analysis (PHA) and PRA to support various safety applications during the design and development process, including evaluating design alternatives, selecting Licensing Basis Events (LBEs), classifying structures, systems, and components (SSCs), and assessing the adequacy of defense-in-depth. | ||
Revision as of 22:33, 5 July 2024
Objective / Purpose
Guidance is focused on surveying and developing sufficient general design criteria such that an AR design complies with licensing requirements developed by the NRC, or another regulatory body such as the CNSC (Canada) or the IAEA (Europe/ Asia). It should also be mentioned that while the IAEA provides useful information regarding the licensing of advanced reactors across different countries, unlike the NRC the IAEA does not produce regulations and does not have any formal research groups to review its findings.
Scope
The NRC has developed several Reg Guides that apply to the adaptation of the Code of Federal Regulations (CFR) 10 Part 50 and 52 for the licensing of non-LWR designs. Additionally, 10 CFR part 54 is currently under development for how it applies to advanced reactor licensing. Please visit the NRC Regulations Title 10 homepage for the full directory of title 10 regulations.
Guidance
In the US, NRC Reg Guide 1.233 [9] provides guidance to applicants who are seeking licenses to operate advanced non-light water reactor nuclear power plants and Reg Guide 1.232 [12] provides guidance on the licensing of non-LWRs from Appendix A of Title 10 Part 50 CFR. Although 10 CFR 50 Appendix A provides some guidance in establishing principal design criteria (PDC) for non-LWR designs, it is the applicant’s responsibility to develop the PDC for its facility based on its design, using generic design criteria, non-LWR design criteria, or other design criteria as the foundation. Similar to Reg Guide 1.232, INL/EXT-14-31179 [12] describes design guidance related to advanced non-light water reactors.
In Canada the CNSC framework for risk-informed decision-making is described in REGDOC-3.5.3 [18]. In 2019, the CNSC and the U.S. NRC signed a memorandum of cooperation (MOC) [19] to increase collaboration on technical reviews of advanced reactor and small modular reactor technologies.
Outside of North America, the IAEA has provided guidance in developing methodologies and safety requirements for AR designs. In particular, the current IAEA safety approach is based on four main pillars that are described and shown in Figure 1 of TECDOC-1570 [16]:
- Qualitative Safety Objectives
- Fundamental Safety Functions
- Defense in Depth
- Probabilistic Safety Assessment
TECDOC-1570 also proposes a new safety approach for ARs based on the review of existing pillars to include any consideration of new technologies and incorporation of probabilistic considerations. In particular, the Safety Goals are identified in terms of consequences as a function of likelihood of occurrence.
In current practice, advanced reactor vendors develop a generic design phase PRA or a reference plant PRA. A Level 1 PRA or both Level 1 and Level 2 PRAs may be requested by the applicable regulatory authority for each new reactor project. A Level 3 PRA is typically not developed or requested by the regulatory authorities for new reactors. However, a Level 3 PRA could support the definition of exclusion zones [25]. In the US, the Licensing Modernization Project (LMP) has developed a methodology that uses standard safety analyses like Process Hazards Analysis (PHA) and PRA to support various safety applications during the design and development process, including evaluating design alternatives, selecting Licensing Basis Events (LBEs), classifying structures, systems, and components (SSCs), and assessing the adequacy of defense-in-depth.